π‘️ Humidity Duct Sensor Installation Methods for Accurate HVAC Measurement Step-by-Step Guide
Welcome to the Insight Control System Blog! π
Humidity control plays a crucial role in HVAC systems, ensuring comfort, energy efficiency, and equipment reliability. In this guide, we’ll explain the correct methods to install humidity duct sensors for accurate measurement and long-term performance. Whether you’re an HVAC technician, engineer, or student, this step-by-step resource will help you achieve precise and reliable readings.
What is a Humidity Duct Sensor?
A Humidity Duct Sensor is a sensing device designed to measure relative humidity (RH) inside air ducts of HVAC (Heating, Ventilation, and Air Conditioning) systems.
These sensors help maintain the right indoor air quality (IAQ) and comfort levels by providing real-time humidity data to building automation or HVAC controllers.
How it Works
- The sensor is installed directly in the air duct (supply or return).
- It uses capacitive or resistive sensing technology to detect the moisture content in the air.
- The measured humidity is converted into an electrical signal (analog or digital).
- The signal is sent to the Building Management System (BMS) or HVAC controller.
- The controller adjusts humidifiers, dehumidifiers, fans, or dampers to maintain desired humidity.
Installation Methods:
![]() |
humidity sensors |
Note:
That humidity sensors are affected by air velocity.
The air velocity in the vicinity of the sensor must not exceed 10 m/sec.
Precaution:
Fit the sensor with a perforated shield or cover (e.g. perforated steel).
Avoid dead-legs. (Super saturation can occur in areas where there is no air flow.)
Important
When installing sensors in ducts with negative pressure, it is possible for air from an external source to be drawn into the device and the installation hole. (Seal tightly to prevent false readings.)
A test hole must be provided for every humidity sensor (downstream of the sensor) Recommended diameter: 40mm.
For maintenance purposes, the electrical connections should be of the plug-in type (e.g. TT45).
Distance for humidification measurements for BM
- BM is the distance between the humidifier and the humidity sensor necessary to allow the air to absorb 100% of the water supplied.
- The required distance depends on the amount of water supplied, the velocity of the air and the type of humidifier system.
- If the humidity sensor is not mounted at the required distance, it will produce a false reading.
Exampleπ
- Because it is in the wrong position, the sensor here measures only 30% of the water or steam introduced into the system, as only this amount has been fully absorbed in gaseous form into the air.
- The sensor element will get wet, produce an incorrect reading, and may be damaged.
Humidification systems
╰┈➤ Air washers - BM downstream of eliminator plate,
╰┈➤ Tray-type humidifier - BM 3.5 m,
╰┈➤ Spray Re-humidifiers - BM 5.5 m,
╰┈➤ Pressurized steam - BM = Isotherm,
╰┈➤ Pressure-free steam - BM = Isotherm 1.3,
╰┈➤ Spray humidifiers,
╰┈➤ Ultrasound humidifiers,
╰┈➤ Centrifugal humidifiers,
╰┈➤ Atomizer humidifiers,
π Related: How to Calculate Humidity and Temperature in a Humidification Plant Using Hygrometers (Step-by-Step Guide)
✅ Distance for adiabatic humidification measurements:This diagram is designed for use in winter, with an absolute humidity content of 1.5 g/kg on the intake side, and a supply air temperature of 18 °C.
π‘ Method
- Enter the air velocity (in m/s) on the left edge of the diagram (e.g. 2.0 m/s).
- From this point, draw a line to the right, along the line indicating the increase in humidity (example: x = 10 g/kg).
- Starting where the two lines intersect, draw a vertical line and read the required distance BM for humidification measurements on the horizontal line at the bottom of the diagram (6.7 m).
Distance BM for humidification measurements with steam humidifiers
- A certain distance is required between humidifier and sensor, so that the air has time to absorb the water (vapor)supplied by the humidifier before the sensor measures the humidity.
- This distance is marked on the diagram as BM.
- The minimum distance between the humidifier and the humidity sensor must be equivalent to at least BM.
π‘ Method
- Enter the increase in humidity in g water/kg air (e.g. 4.5 g/kg) on the right edge of the diagram.
- Draw a horizontal line extending from this point towards the left.
- Enter the minimum duct air velocity (in m/s) on the bottom edge of the diagram (e.g. 1.9 m/s) and draw a vertical line extending upwards from this point.
- From the point of intersection of these two lines, draw a diagonal line extending upwards and parallel to the existing diagonals. Read the distance BM in metres, from the scale on the edge of the diagram (example 8.5 m).
- Enter the minimum duct air velocity (in m/s) on the bottom edge of the diagram (e.g. 1.9 m/s) and draw a vertical line extending upwards from this point.
- From the point of intersection of these two lines, draw a diagonal line extending upwards and parallel to the existing diagonals.
- Read the distance, BM, in metres, from the scale on the edge of the diagram (example 8.5 m).
Average humidity measurement
Locating the humidity sensor in a bypass duct improves the measurement of average, relative or absolute humidity and should be used:
- In cases of temperature or humidity stratification.
- Here too, the appropriate distance for humidity measurements BM must be maintained.
Humidity Room Sensor
Install sensors at a height of 1.5 m in occupied spaces, and at least 50 cm from the adjacent wall.
Seal gaps between cable/plastic tubing and conduit.
Otherwise, measurements will be falsified by incorrect circulation of the air.
Applications
π― Conclusion
Proper installation of humidity duct sensors ensures reliable HVAC performance, prevents equipment damage, and maintains ideal indoor conditions.
π‘ Whether you’re designing a new system or upgrading an existing one, following these guidelines will help you avoid errors and achieve accurate humidity measurements.
π² For more tips on HVAC automation and sensor technologies, follow us on our social media channels and explore our other guides. Don’t forget to share your thoughts in the comments below we’d love to hear your experiences!
π Stay tuned for Part 2 of our series, where we’ll cover advanced calibration techniques and troubleshooting methods.
π Related: Fan Coil Unit (FCU) Installation in HVAC Systems Step-by-Step Method Statement for Professionals
π Related: Method Statement for HVAC Fan Installation Floor & Ceiling Mounted Systems Step-by-Step Guide
π Related: Spiral Round Ducting Installation Methods for HVAC Systems
π Related: How a Chiller System Works Complete Working Principle and Key Components